Skip to main content

Analog Input Object - Lamp Feedback

These Analog Input objects report the feedback of the five lamp. All values are expressed as a percentage from 0 to 100.

Objects​

TypeInstanceNameMinimumMaximumUnitPhysical signal
AI5LAMP 1 FB0100percentLamp 1
AI6LAMP 2 FB0100percentLamp 2
AI7LAMP 3 FB0100percentLamp 3
AI8LAMP 4 FB0100percentLamp 4
AI9LAMP 5 FB0100percentLamp 5

Properties​

List of available properties for the Analog Input objects.

Property IdentifierProperty IDProperty DatatypeWritable / Read-only
Object_Identifier75BACnetObjectIdentifierR
Object_Name77CharacterStringR
Object_Type79BACnetObjectTypeR
Present_Value85REALR (1)
Status_Flags111BACnetStatusFlagsR
Event_State36BACnetEventStateR
Out_Of_Service81BOOLEANW
Units117BACnetEngineeringUnitsR
Property_List371BACnetARRAY of UnsignedR
Description28CharacterStringR
Reliability103BACnetReliabilityR (1)
Min_Pres_Value69REALR
Max_Pres_Value65REALR
COV_Increment22REALW
Reliability_Evaluation_Inhibit357BOOLEANW
  1. This property is writable when Out_Of_Service is TRUE.