The Analog Value objects hold the analog setpoints and computed analog values: the daylight setpoints, the network light inputs, the band-2 lamp feedback, and the per-control-output power limit and light value.
Some Analog Value objects are commandable (daylight setpoints and power limits) and expose a priority array. The others are read-only computed values.
Daylight Setpoints
Objects
| Type | Instance | Name | Unit |
|---|
| AV | 0 | DAYLIGHT SETPOINT UNOCC 1 | luxes |
| AV | 1 | DAYLIGHT SETPOINT 1 | luxes |
| AV | 2 | DAYLIGHT SETPOINT UNOCC 2 | luxes |
| AV | 3 | DAYLIGHT SETPOINT 2 | luxes |
Objects
| Type | Instance | Name | Unit |
|---|
| AV | 4 | INPUT LIGHT 1 | no-units |
| AV | 5 | INPUT LIGHT 2 | no-units |
| AV | 8 | INPUT LIGHT 3 | no-units |
| AV | 9 | INPUT LIGHT 4 | no-units |
Lamp Band 2 Feedback
Objects
| Type | Instance | Name | Minimum | Maximum | Unit |
|---|
| AV | 6 | LAMP BAND 2-1 FB | 0 | 100 | percent |
| AV | 7 | LAMP BAND 2-2 FB | 0 | 100 | percent |
Control Output Power Limit
Objects
| Type | Instance | Name | Minimum | Maximum | Unit |
|---|
| AV | 101 | CONTROL OUTPUT 1 - POWER LIMIT | 0 | 100 | percent |
| AV | 201 | CONTROL OUTPUT 2 - POWER LIMIT | 0 | 100 | percent |
| AV | 301 | CONTROL OUTPUT 3 - POWER LIMIT | 0 | 100 | percent |
| AV | 401 | CONTROL OUTPUT 4 - POWER LIMIT | 0 | 100 | percent |
| AV | 501 | CONTROL OUTPUT 5 - POWER LIMIT | 0 | 100 | percent |
Control Output Light Value
Objects
| Type | Instance | Name | Unit |
|---|
| AV | 100 | CONTROL OUTPUT 1 - LIGHT VALUE | luxes |
| AV | 200 | CONTROL OUTPUT 2 - LIGHT VALUE | luxes |
| AV | 300 | CONTROL OUTPUT 3 - LIGHT VALUE | luxes |
| AV | 400 | CONTROL OUTPUT 4 - LIGHT VALUE | luxes |
| AV | 500 | CONTROL OUTPUT 5 - LIGHT VALUE | luxes |
Properties
List of available properties for the Analog Value objects.
| Property Identifier | Property ID | Property Datatype | Writable / Read-only |
|---|
| Object_Identifier | 75 | BACnetObjectIdentifier | R |
| Object_Name | 77 | CharacterString | R |
| Object_Type | 79 | BACnetObjectType | R |
| Present_Value | 85 | REAL | W (1) |
| Status_Flags | 111 | BACnetStatusFlags | R |
| Event_State | 36 | BACnetEventState | R |
| Out_Of_Service | 81 | BOOLEAN | W |
| Units | 117 | BACnetEngineeringUnits | R |
| Property_List | 371 | BACnetARRAY of Unsigned | R |
| Description | 28 | CharacterString | R |
| Reliability | 103 | BACnetReliability | R |
| Min_Pres_Value | 69 | REAL | R |
| Max_Pres_Value | 65 | REAL | R |
| COV_Increment | 22 | REAL | W |
| Priority_Array | 87 | BACnetPriorityArray | R (2) |
| Relinquish_Default | 104 | REAL | R (2) |
-
Present_Value is writable on the commandable objects (daylight setpoints and power limits) and read-only on the computed feedback objects (input light, lamp band feedback, and light value).
-