Skip to main content

Binary Input Object - Relay Feedback

The Binary Input relay feedback objects report the actual state of the five relay outputs.

Objects​

TypeInstanceName
BI8RELAY 1 FB
BI9RELAY 2 FB
BI10RELAY 3 FB
BI11RELAY 4 FB
BI12RELAY 5 FB

Properties​

List of available properties for the Binary Input objects.

Property IdentifierProperty IDProperty DatatypeWritable / Read-only
Object_Identifier75BACnetObjectIdentifierR
Object_Name77CharacterStringR
Object_Type79BACnetObjectTypeR
Present_Value85BACnetBinaryPVR (1)
Status_Flags111BACnetStatusFlagsR
Event_State36BACnetEventStateR
Out_Of_Service81BOOLEANW
Polarity84BACnetPolarityR
Property_List371BACnetARRAY of UnsignedR
Description28CharacterStringR
Reliability103BACnetReliabilityR
Active_Text4CharacterStringR
Inactive_Text46CharacterStringR
  1. This property is writable when Out_Of_Service is TRUE.