Skip to main content

Binary Value Object - Occupied Mode

The Occupied Mode binary value objects hold the occupancy mode used by the controller. These objects are commandable. Each OCCUPIED MODE object commands the occupancy of its associated Control Output.

Objects​

TypeInstanceNameControl Output
BV0OCCUPIED MODE 1Control Output 1
BV1OCCUPIED MODE 2Control Output 2
BV18OCCUPIED MODE 3Control Output 3
BV19OCCUPIED MODE 4Control Output 4
BV20OCCUPIED MODE 5Control Output 5

Properties​

List of available properties for the Occupied Mode objects. Properties with an identifier of 512 or higher are proprietary.

Property IdentifierProperty IDProperty DatatypeWritable / Read-only
Object_Identifier75BACnetObjectIdentifierR
Object_Name77CharacterStringR
Object_Type79BACnetObjectTypeR
Present_Value85BACnetBinaryPVW (commandable)
Status_Flags111BACnetStatusFlagsR
Event_State36BACnetEventStateR
Out_Of_Service81BOOLEANW
Priority_Array87BACnetPriorityArrayR
Relinquish_Default104BACnetBinaryPVR
Property_List371BACnetARRAY of UnsignedR
Description28CharacterStringR
Reliability103BACnetReliabilityR
Active_Text4CharacterStringR
Inactive_Text46CharacterStringR
Group_Command_Allowed532EnumeratedW

Proprietary Properties​

Group_Command_Allowed (532)​

Controls whether the controller operation is allowed to drive the occupancy mode. It gates only the internal sources, such as occupancy sensors, schedule and network inputs, and does not restrict a direct BACnet write to Present_Value. The values are as follows:

  • 0 - the operation cannot set the mode active or inactive.
  • 1 - the operation can only set the mode inactive.
  • 2 - the operation can only set the mode active.
  • 3 - the operation can set the mode active or inactive.

The default value is 3.