Skip to main content

Multi-State Value Object - Sequence Control

The sequence control multi-state value object selects the active operating sequence.

Objects​

TypeInstanceName
MSV1000SEQUENCE CONTROL

Properties​

List of available properties for the sequence control object.

Property IdentifierProperty IDProperty DatatypeWritable / Read-only
Object_Identifier75BACnetObjectIdentifierR
Object_Name77CharacterStringR
Object_Type79BACnetObjectTypeR
Present_Value85UnsignedW
Status_Flags111BACnetStatusFlagsR
Event_State36BACnetEventStateR
Out_Of_Service81BOOLEANW
Number_Of_States74UnsignedR
Property_List371BACnetARRAY of UnsignedR
Description28CharacterStringR
State_Text110BACnetARRAY of CharacterStringR

State text​

The State_Text property maps each Present_Value to a text label.

Present_ValueState_TextDescription
1NO COMMANDNo command
2 to 17START 1 to START 16Start sequence 1 to 16
18 to 33STOP 1 to STOP 16Stop sequence 1 to 16
34 to 49PAUSE 1 to PAUSE 16Pause sequence 1 to 16
50 to 65RESUME 1 to RESUME 16Resume sequence 1 to 16