BACnet

BACnet MS/TP​

BACnet MS/TP allows the configuration of the controller via the BACnet Browser software from Cristal Controls. Multiple BACnet objects exist to allow for the integration of the controller into a BACnet system.

When at the end of a RS-485 network, we may enable the 120 Ω terminating resistor by activating the TERM dipswitch to terminate the network. The dipswitches BIAS+ and BIAS- allow enabling 604 Ω pull-up and pull-down bias.

For more RS-485 network information, refer to the Cristal Controls “Setting up a RS-485 Network” manual. Go to our website or call customer service to get a PDF copy.

BACnet Objects​

Many objects allow direct control on inputs and outputs of the controller. The table below lists every object. For the full property list of each object, including the proprietary properties, see the BACnet Objects reference pages.

TypeInstanceNameMinimumMaximumUnitPhysical signalNote
Device72CC-ONYX    
AI0OUTPUT 0-10V 1 FB0100percent0-10V + (1)
AI1OUTPUT 0-10V 2 FB0100percent0-10V + (2)
AI2INPUT 0-10V 10100percentAI1 - DAYLIGHT 1
AI3INPUT 0-10V 20100percentAI2 - DAYLIGHT 2
AI424VDC FB0100percent+24V OUT
AI5LAMP 1 FB0100percentLamp 1
AI6LAMP 2 FB0100percentLamp 2
AI7LAMP 3 FB0100percentLamp 3
AI8LAMP 4 FB0100percentLamp 4
AI9LAMP 5 FB0100percentLamp 5
AO0OUTPUT 0-10V 10100percentOUTPUT 0-10V 1
AO1OUTPUT 0-10V 20100percentOUTPUT 0-10V 2
AO2LAMP 1 CMD0100percent
AO3LAMP 2 CMD0100percent
AO4LAMP 3 CMD0100percent
AO5LAMP 4 CMD0100percent
AO6LAMP 5 CMD0100percent
AV0DAYLIGHT SETPOINT UNOCC 1  luxes
AV1DAYLIGHT SETPOINT 1  luxes
AV2DAYLIGHT SETPOINT UNOCC 2  luxes
AV3DAYLIGHT SETPOINT 2  luxes
AV4INPUT LIGHT 1  no-units
AV5INPUT LIGHT 2  no-units
AV8INPUT LIGHT 3  no-units
AV9INPUT LIGHT 4  no-units
AV6LAMP BAND 2-1 FB0100percent
AV7LAMP BAND 2-2 FB0100percent
AV101CONTROL OUTPUT 1 - POWER LIMIT0100percent
AV201CONTROL OUTPUT 2 - POWER LIMIT0100percent
AV301CONTROL OUTPUT 3 - POWER LIMIT0100percent
AV401CONTROL OUTPUT 4 - POWER LIMIT0100percent
AV501CONTROL OUTPUT 5 - POWER LIMIT0100percent
AV100CONTROL OUTPUT 1 - LIGHT VALUE  luxes
AV200CONTROL OUTPUT 2 - LIGHT VALUE  luxes
AV300CONTROL OUTPUT 3 - LIGHT VALUE  luxes
AV400CONTROL OUTPUT 4 - LIGHT VALUE  luxes
AV500CONTROL OUTPUT 5 - LIGHT VALUE  luxes
BI0DIGITAL INPUT 1DI1 - SWITCH 1
BI1DIGITAL INPUT 2DI2 - SWITCH 2
BI2DIGITAL INPUT 3DI3 - SWITCH 3
BI3DIGITAL INPUT 4DI4 - SWITCH 4
BI4DIGITAL INPUT 5DI5 - OCCUPANCY 1
BI5DIGITAL INPUT 6DI6 - AUX IN 1
BI6DIGITAL INPUT 7DI7 - AUX IN 2
BI7DIGITAL INPUT 8DI8 - OCCUPANCY 2
BI8RELAY 1 FB   
BI9RELAY 2 FB   
BI10RELAY 3 FB   
BI11RELAY 4 FB   
BI12RELAY 5 FB   
BI13BUTTON LOCAL STATUS   
BI14BUTTON LOCAL 1   
BI15BUTTON LOCAL 2   
BI16BUTTON LOCAL 3   
BI17BUTTON LOCAL 4   
BI18BUTTON LOCAL 5   
BO0RELAY 1 CMDK1
BO1RELAY 2 CMDK2
BO2RELAY 3 CMDRELAY 3 AUX
BO3RELAY 4 CMDRELAY 4 AUX
BO4RELAY 5 CMDRELAY 5 AUX
BV0OCCUPIED MODE 1   
BV1OCCUPIED MODE 2   
BV2NETWORK DIGITAL INPUT 1   
BV3NETWORK DIGITAL INPUT 2   
BV4NETWORK DIGITAL INPUT 3   
BV5NETWORK DIGITAL INPUT 4   
BV6NETWORK DIGITAL INPUT 5   
BV7NETWORK DIGITAL INPUT 6   
BV8NETWORK DIGITAL INPUT 7   
BV9NETWORK DIGITAL INPUT 8   
BV10NETWORK DIGITAL INPUT 9   
BV11NETWORK DIGITAL INPUT 10   
BV12NETWORK DIGITAL INPUT 11   
BV13NETWORK DIGITAL INPUT 12   
BV14NETWORK DIGITAL INPUT 13   
BV15NETWORK DIGITAL INPUT 14   
BV16NETWORK DIGITAL INPUT 15   
BV17NETWORK DIGITAL INPUT 16   
BV19OCCUPIED MODE 4
BV20OCCUPIED MODE 5
BV200CONTROL OUTPUT 2 - OCCUPANCY STATE   
BV300CONTROL OUTPUT 3 - OCCUPANCY STATE   
BV400CONTROL OUTPUT 4 - OCCUPANCY STATE   
BV500CONTROL OUTPUT 5 - OCCUPANCY STATE   
MSV0SCENE CONTROL LOCAL 1   
MSV1SCENE CONTROL LOCAL 2   
MSV2SCENE CONTROL LOCAL 3   
MSV3SCENE CONTROL LOCAL 4   
MSV4SCENE CONTROL LOCAL 5   
MSV100CONTROL OUTPUT 1 - ACTIVE SCENE   
MSV200CONTROL OUTPUT 2 - ACTIVE SCENE   
MSV300CONTROL OUTPUT 3 - ACTIVE SCENE   
MSV400CONTROL OUTPUT 4 - ACTIVE SCENE   
MSV500CONTROL OUTPUT 5 - ACTIVE SCENE   
MSV1000SEQUENCE CONTROL   
MSV1001SCHEDULE CONTROL   
Channel1CHANNEL 1   
Channel2CHANNEL 2   
Channel3CHANNEL 3   
Channel4CHANNEL 4   
File0ConfigSystem.bin   
File1ConfigOutput.bin   
File2ConfigScheduler.bin   
File3syslog.txt   
File4syslog_old.txt   
File5ConfigDataPolling.bin   
File6ConfigSequencer.bin   
File7ConfigNames.bin   
File100Flash.bin   
File101FlashFS.bin   
File102FlashRaw.bin   
File103ConfigBoard.bin   

BACnet Browser Configuration Software​

BACnet Browser is a configuration software available for the Windows operating system and available on the Cristal Controls website. It allows the configuration of all the parameters of the room controller.