BACnet
BACnet MS/TP
BACnet MS/TP allows the configuration of the controller via the BACnet Browser software from Cristal Controls. Multiple BACnet objects exist to allow for the integration of the controller into a BACnet system.
When at the end of a RS-485 network, we may enable the 120 Ω terminating resistor by activating the TERM dipswitch to terminate the network. The dipswitches BIAS+ and BIAS- allow enabling 604 Ω pull-up and pull-down bias.
For more RS-485 network information, refer to the Cristal Controls “Setting up a RS-485 Network” manual. Go to our website or call customer service to get a PDF copy.
BACnet Objects
Many objects allow direct control on inputs and outputs of the controller. The table below lists every object. For the full property list of each object, including the proprietary properties, see the BACnet Objects reference pages.
| Type | Instance | Name | Minimum | Maximum | Unit | Physical signal | Note |
|---|---|---|---|---|---|---|---|
| Device | 72 | CC-ONYX | |||||
| AI | 0 | OUTPUT 0-10V 1 FB | 0 | 100 | percent | 0-10V + (1) | |
| AI | 1 | OUTPUT 0-10V 2 FB | 0 | 100 | percent | 0-10V + (2) | |
| AI | 2 | INPUT 0-10V 1 | 0 | 100 | percent | AI1 - DAYLIGHT 1 | |
| AI | 3 | INPUT 0-10V 2 | 0 | 100 | percent | AI2 - DAYLIGHT 2 | |
| AI | 4 | 24VDC FB | 0 | 100 | percent | +24V OUT | |
| AI | 5 | LAMP 1 FB | 0 | 100 | percent | Lamp 1 | |
| AI | 6 | LAMP 2 FB | 0 | 100 | percent | Lamp 2 | |
| AI | 7 | LAMP 3 FB | 0 | 100 | percent | Lamp 3 | |
| AI | 8 | LAMP 4 FB | 0 | 100 | percent | Lamp 4 | |
| AI | 9 | LAMP 5 FB | 0 | 100 | percent | Lamp 5 | |
| AO | 0 | OUTPUT 0-10V 1 | 0 | 100 | percent | OUTPUT 0-10V 1 | |
| AO | 1 | OUTPUT 0-10V 2 | 0 | 100 | percent | OUTPUT 0-10V 2 | |
| AO | 2 | LAMP 1 CMD | 0 | 100 | percent | ||
| AO | 3 | LAMP 2 CMD | 0 | 100 | percent | ||
| AO | 4 | LAMP 3 CMD | 0 | 100 | percent | ||
| AO | 5 | LAMP 4 CMD | 0 | 100 | percent | ||
| AO | 6 | LAMP 5 CMD | 0 | 100 | percent | ||
| AV | 0 | DAYLIGHT SETPOINT UNOCC 1 | luxes | ||||
| AV | 1 | DAYLIGHT SETPOINT 1 | luxes | ||||
| AV | 2 | DAYLIGHT SETPOINT UNOCC 2 | luxes | ||||
| AV | 3 | DAYLIGHT SETPOINT 2 | luxes | ||||
| AV | 4 | INPUT LIGHT 1 | no-units | ||||
| AV | 5 | INPUT LIGHT 2 | no-units | ||||
| AV | 8 | INPUT LIGHT 3 | no-units | ||||
| AV | 9 | INPUT LIGHT 4 | no-units | ||||
| AV | 6 | LAMP BAND 2-1 FB | 0 | 100 | percent | ||
| AV | 7 | LAMP BAND 2-2 FB | 0 | 100 | percent | ||
| AV | 101 | CONTROL OUTPUT 1 - POWER LIMIT | 0 | 100 | percent | ||
| AV | 201 | CONTROL OUTPUT 2 - POWER LIMIT | 0 | 100 | percent | ||
| AV | 301 | CONTROL OUTPUT 3 - POWER LIMIT | 0 | 100 | percent | ||
| AV | 401 | CONTROL OUTPUT 4 - POWER LIMIT | 0 | 100 | percent | ||
| AV | 501 | CONTROL OUTPUT 5 - POWER LIMIT | 0 | 100 | percent | ||
| AV | 100 | CONTROL OUTPUT 1 - LIGHT VALUE | luxes | ||||
| AV | 200 | CONTROL OUTPUT 2 - LIGHT VALUE | luxes | ||||
| AV | 300 | CONTROL OUTPUT 3 - LIGHT VALUE | luxes | ||||
| AV | 400 | CONTROL OUTPUT 4 - LIGHT VALUE | luxes | ||||
| AV | 500 | CONTROL OUTPUT 5 - LIGHT VALUE | luxes | ||||
| BI | 0 | DIGITAL INPUT 1 | DI1 - SWITCH 1 | ||||
| BI | 1 | DIGITAL INPUT 2 | DI2 - SWITCH 2 | ||||
| BI | 2 | DIGITAL INPUT 3 | DI3 - SWITCH 3 | ||||
| BI | 3 | DIGITAL INPUT 4 | DI4 - SWITCH 4 | ||||
| BI | 4 | DIGITAL INPUT 5 | DI5 - OCCUPANCY 1 | ||||
| BI | 5 | DIGITAL INPUT 6 | DI6 - AUX IN 1 | ||||
| BI | 6 | DIGITAL INPUT 7 | DI7 - AUX IN 2 | ||||
| BI | 7 | DIGITAL INPUT 8 | DI8 - OCCUPANCY 2 | ||||
| BI | 8 | RELAY 1 FB | |||||
| BI | 9 | RELAY 2 FB | |||||
| BI | 10 | RELAY 3 FB | |||||
| BI | 11 | RELAY 4 FB | |||||
| BI | 12 | RELAY 5 FB | |||||
| BI | 13 | BUTTON LOCAL STATUS | |||||
| BI | 14 | BUTTON LOCAL 1 | |||||
| BI | 15 | BUTTON LOCAL 2 | |||||
| BI | 16 | BUTTON LOCAL 3 | |||||
| BI | 17 | BUTTON LOCAL 4 | |||||
| BI | 18 | BUTTON LOCAL 5 | |||||
| BO | 0 | RELAY 1 CMD | K1 | ||||
| BO | 1 | RELAY 2 CMD | K2 | ||||
| BO | 2 | RELAY 3 CMD | RELAY 3 AUX | ||||
| BO | 3 | RELAY 4 CMD | RELAY 4 AUX | ||||
| BO | 4 | RELAY 5 CMD | RELAY 5 AUX | ||||
| BV | 0 | OCCUPIED MODE 1 | |||||
| BV | 1 | OCCUPIED MODE 2 | |||||
| BV | 2 | NETWORK DIGITAL INPUT 1 | |||||
| BV | 3 | NETWORK DIGITAL INPUT 2 | |||||
| BV | 4 | NETWORK DIGITAL INPUT 3 | |||||
| BV | 5 | NETWORK DIGITAL INPUT 4 | |||||
| BV | 6 | NETWORK DIGITAL INPUT 5 | |||||
| BV | 7 | NETWORK DIGITAL INPUT 6 | |||||
| BV | 8 | NETWORK DIGITAL INPUT 7 | |||||
| BV | 9 | NETWORK DIGITAL INPUT 8 | |||||
| BV | 10 | NETWORK DIGITAL INPUT 9 | |||||
| BV | 11 | NETWORK DIGITAL INPUT 10 | |||||
| BV | 12 | NETWORK DIGITAL INPUT 11 | |||||
| BV | 13 | NETWORK DIGITAL INPUT 12 | |||||
| BV | 14 | NETWORK DIGITAL INPUT 13 | |||||
| BV | 15 | NETWORK DIGITAL INPUT 14 | |||||
| BV | 16 | NETWORK DIGITAL INPUT 15 | |||||
| BV | 17 | NETWORK DIGITAL INPUT 16 | |||||
| BV | 19 | OCCUPIED MODE 4 | |||||
| BV | 20 | OCCUPIED MODE 5 | |||||
| BV | 200 | CONTROL OUTPUT 2 - OCCUPANCY STATE | |||||
| BV | 300 | CONTROL OUTPUT 3 - OCCUPANCY STATE | |||||
| BV | 400 | CONTROL OUTPUT 4 - OCCUPANCY STATE | |||||
| BV | 500 | CONTROL OUTPUT 5 - OCCUPANCY STATE | |||||
| MSV | 0 | SCENE CONTROL LOCAL 1 | |||||
| MSV | 1 | SCENE CONTROL LOCAL 2 | |||||
| MSV | 2 | SCENE CONTROL LOCAL 3 | |||||
| MSV | 3 | SCENE CONTROL LOCAL 4 | |||||
| MSV | 4 | SCENE CONTROL LOCAL 5 | |||||
| MSV | 100 | CONTROL OUTPUT 1 - ACTIVE SCENE | |||||
| MSV | 200 | CONTROL OUTPUT 2 - ACTIVE SCENE | |||||
| MSV | 300 | CONTROL OUTPUT 3 - ACTIVE SCENE | |||||
| MSV | 400 | CONTROL OUTPUT 4 - ACTIVE SCENE | |||||
| MSV | 500 | CONTROL OUTPUT 5 - ACTIVE SCENE | |||||
| MSV | 1000 | SEQUENCE CONTROL | |||||
| MSV | 1001 | SCHEDULE CONTROL | |||||
| Channel | 1 | CHANNEL 1 | |||||
| Channel | 2 | CHANNEL 2 | |||||
| Channel | 3 | CHANNEL 3 | |||||
| Channel | 4 | CHANNEL 4 | |||||
| File | 0 | ConfigSystem.bin | |||||
| File | 1 | ConfigOutput.bin | |||||
| File | 2 | ConfigScheduler.bin | |||||
| File | 3 | syslog.txt | |||||
| File | 4 | syslog_old.txt | |||||
| File | 5 | ConfigDataPolling.bin | |||||
| File | 6 | ConfigSequencer.bin | |||||
| File | 7 | ConfigNames.bin | |||||
| File | 100 | Flash.bin | |||||
| File | 101 | FlashFS.bin | |||||
| File | 102 | FlashRaw.bin | |||||
| File | 103 | ConfigBoard.bin |
BACnet Browser Configuration Software
BACnet Browser is a configuration software available for the Windows operating system and available on the Cristal Controls website. It allows the configuration of all the parameters of the room controller.