CC-ONYX Quick Installation Sheet
Use this sheet to quickly configure operation with the 8-position SCENARIOS dipswitch and use Test Mode for faster commissioning.
Operation Dipswitches
Configuration Tool
ON
12345678
Configuration
1Room Type
RT2Occupancy Timeout
TD3Occupancy / Vacancy Mode
OS4Occupied Level
OC5Unoccupied Level
UC6Daylight Harvesting
DL7+8Switch Mode
SMConfiguration ID:
RT1-TDS-OSO-OCH-UCO-DL0-SM1Wall Switch Behavior
SM1RT1Supported: 2 or 4 buttons
Button 1 SWITCH #1
ON / Up [lo1, lo3]
Start Daylight / Up [lo1]
Button 2 SWITCH #2
OFF / Down [lo1, lo3]
Button 3 SWITCH #3
ON / Up [lo2, lo4]
Button 4 SWITCH #4
OFF / Down [lo2, lo4]
[lo1] = 0-10V #1 [lo2] = 0-10V #2 [lo3] = AUX_OUT_1 [lo4] = AUX_OUT_2
Reference Table
| Position | Function | OFF (factory default) | ON |
|---|---|---|---|
| 1 | Room Type | 1 room | 2 rooms |
| 2 | Occupancy Timeout | 20 minutes | 40 minutes |
| 3 | Occupancy / Vacancy Mode | Occupancy, Auto ON / Auto OFF | Vacancy, Manual ON / Auto OFF |
| 4 | Occupied Level | 100% when occupied (400 lux setpoint if daylight enabled) | 50% when occupied (250 lux setpoint if daylight enabled) |
| 5 | Unoccupied Level | OFF when vacant | 50% when vacant |
| 6 | Daylight Harvesting | Daylight disabled | Daylight enabled |
| 7+8 | Switch Mode | ON/OFF (7=OFF 8=OFF) | Last Level/OFF (7=ON 8=OFF) |
| 4-button (1 Room only) (7=OFF 8=ON) | Reserved (7=ON 8=ON) |
Wall Switch Operation Dipswitches
Wall switch behavior depends on Room Type and the selected Switch Mode.
Reference Table
ON/OFF (Position 7: OFF, Position 8: OFF)
Supported by 2 or 4 buttons
| Button 1 (SWITCH #1) | Button 2 (SWITCH #2) | Button 3 (SWITCH #3) | Button 4 (SWITCH #4) | |
|---|---|---|---|---|
| 1 Room | ON / Up [lo1, lo3] Start Daylight / Up [lo1] | OFF / Down [lo1, lo3] | ON / Up [lo2, lo4] | OFF / Down [lo2, lo4] |
| 2 Rooms | ON / Up [lo1, lo3] Start Daylight / Up [lo1] | OFF / Down [lo1, lo3] | ON / Up [lo2, lo4] Start Daylight / Up [lo2] | OFF / Down [lo2, lo4] |
Last Level/OFF (Position 7: ON, Position 8: OFF)
Supported by 2 or 4 buttons
| Button 1 (SWITCH #1) | Button 2 (SWITCH #2) | Button 3 (SWITCH #3) | Button 4 (SWITCH #4) | |
|---|---|---|---|---|
| 1 Room | Last Level / Up [lo1, lo3] Start Daylight / Up [lo1] | OFF / Down [lo1, lo3] | Last Level / Up [lo2, lo4] | OFF / Down [lo2, lo4] |
| 2 Rooms | Last Level / Up [lo1, lo3] Start Daylight / Up [lo1] | OFF / Down [lo1, lo3] | Last Level / Up [lo2, lo4] Start Daylight / Up [lo2] | OFF / Down [lo2, lo4] |
4-button (Position 7: OFF, Position 8: ON)
Supported by 4 buttons - 1 Room only
| Button 1 (SWITCH #1) | Button 2 (SWITCH #2) | Button 3 (SWITCH #3) | Button 4 (SWITCH #4) | |
|---|---|---|---|---|
| 1 Room | ON [lo1, lo3, lo2, lo4] Start Daylight [lo1] | Up [lo1, lo3, lo2, lo4] | Down [lo1, lo3, lo2, lo4] | OFF [lo1, lo3, lo2, lo4] |
| 2 Rooms | Reserved | Reserved | Reserved | Reserved |
Reserved (Position 7: ON, Position 8: ON)
No wall switch function assigned.
Output legend: [lo1] = 0-10V #1 · [lo2] = 0-10V #2 · [lo3] = AUX_OUT_1 · [lo4] = AUX_OUT_2
Test Mode
Test Mode is used to speed up commissioning and walk testing. When enabled, occupancy related delays are reduced to a maximum of about 10 seconds.
To enable Test Mode:
- Press the button
STATUSandButton 1together. - Test Mode is triggered immediately when both buttons are pressed.
- Recommended gesture: press and hold one button, press the second button, then release both.
- When Test Mode is active, the status LED blinks faster.
- Test Mode is deactivated automatically after 15 minutes.
- You can also deactivate Test Mode manually using the same two buttons combination.