Skip to main content

CC-ONYX Quick Installation Sheet

Use this sheet to quickly configure operation with the 8-position SCENARIOS dipswitch and use Test Mode for faster commissioning.

Operation Dipswitches​

Configuration Tool​

ON
12345678
Configuration
1Room TypeRT
2Occupancy TimeoutTD
3Occupancy / Vacancy ModeOS
4Occupied LevelOC
5Unoccupied LevelUC
6Daylight HarvestingDL
7+8Switch ModeSM
Configuration ID:RT1-TDS-OSO-OCH-UCO-DL0-SM1
Wall Switch BehaviorSM1RT1
Supported: 2 or 4 buttons
Button 1 SWITCH #1
ON / Up [lo1, lo3]
Start Daylight / Up [lo1]
Button 2 SWITCH #2
OFF / Down [lo1, lo3]
Button 3 SWITCH #3
ON / Up [lo2, lo4]
Button 4 SWITCH #4
OFF / Down [lo2, lo4]
[lo1] = 0-10V #1   [lo2] = 0-10V #2   [lo3] = AUX_OUT_1   [lo4] = AUX_OUT_2

Reference Table​

PositionFunctionOFF (factory default) ON
1Room Type1 room2 rooms
2Occupancy Timeout20 minutes40 minutes
3Occupancy / Vacancy ModeOccupancy, Auto ON / Auto OFFVacancy, Manual ON / Auto OFF
4Occupied Level100% when occupied
(400 lux setpoint if daylight enabled)
50% when occupied
(250 lux setpoint if daylight enabled)
5Unoccupied LevelOFF when vacant50% when vacant
6Daylight HarvestingDaylight disabledDaylight enabled
7+8Switch ModeON/OFF (7=OFF 8=OFF)Last Level/OFF (7=ON 8=OFF)
4-button (1 Room only) (7=OFF 8=ON)Reserved (7=ON 8=ON)

Wall Switch Operation Dipswitches​

Wall switch behavior depends on Room Type and the selected Switch Mode.

Reference Table​

ON/OFF (Position 7: OFF, Position 8: OFF)​

Supported by 2 or 4 buttons

Button 1 (SWITCH #1)Button 2 (SWITCH #2)Button 3 (SWITCH #3)Button 4 (SWITCH #4)
1 RoomON / Up [lo1, lo3]
Start Daylight / Up [lo1]
OFF / Down [lo1, lo3]ON / Up [lo2, lo4]OFF / Down [lo2, lo4]
2 RoomsON / Up [lo1, lo3]
Start Daylight / Up [lo1]
OFF / Down [lo1, lo3]ON / Up [lo2, lo4]
Start Daylight / Up [lo2]
OFF / Down [lo2, lo4]

Last Level/OFF (Position 7: ON, Position 8: OFF)​

Supported by 2 or 4 buttons

Button 1 (SWITCH #1)Button 2 (SWITCH #2)Button 3 (SWITCH #3)Button 4 (SWITCH #4)
1 RoomLast Level / Up [lo1, lo3]
Start Daylight / Up [lo1]
OFF / Down [lo1, lo3]Last Level / Up [lo2, lo4]OFF / Down [lo2, lo4]
2 RoomsLast Level / Up [lo1, lo3]
Start Daylight / Up [lo1]
OFF / Down [lo1, lo3]Last Level / Up [lo2, lo4]
Start Daylight / Up [lo2]
OFF / Down [lo2, lo4]

4-button (Position 7: OFF, Position 8: ON)​

Supported by 4 buttons - 1 Room only

Button 1 (SWITCH #1)Button 2 (SWITCH #2)Button 3 (SWITCH #3)Button 4 (SWITCH #4)
1 RoomON [lo1, lo3, lo2, lo4]
Start Daylight [lo1]
Up [lo1, lo3, lo2, lo4]Down [lo1, lo3, lo2, lo4]OFF [lo1, lo3, lo2, lo4]
2 RoomsReservedReservedReservedReserved

Reserved (Position 7: ON, Position 8: ON)​

No wall switch function assigned.

Output legend: [lo1] = 0-10V #1 · [lo2] = 0-10V #2 · [lo3] = AUX_OUT_1 · [lo4] = AUX_OUT_2

Test Mode​

Test Mode is used to speed up commissioning and walk testing. When enabled, occupancy related delays are reduced to a maximum of about 10 seconds.

To enable Test Mode:

  1. Press the button STATUS and Button 1 together.
  2. Test Mode is triggered immediately when both buttons are pressed.
  3. Recommended gesture: press and hold one button, press the second button, then release both.
  • When Test Mode is active, the status LED blinks faster.
  • Test Mode is deactivated automatically after 15 minutes.