Skip to main content

Binary Value Object - Network Digital Inputs

The Network Digital Input binary value objects let a BACnet client provide up to sixteen virtual digital inputs to the CC-ONYX controller. These objects are commandable.

Objects​

TypeInstanceName
BV2NETWORK DIGITAL INPUT 1
BV3NETWORK DIGITAL INPUT 2
BV4NETWORK DIGITAL INPUT 3
BV5NETWORK DIGITAL INPUT 4
BV6NETWORK DIGITAL INPUT 5
BV7NETWORK DIGITAL INPUT 6
BV8NETWORK DIGITAL INPUT 7
BV9NETWORK DIGITAL INPUT 8
BV10NETWORK DIGITAL INPUT 9
BV11NETWORK DIGITAL INPUT 10
BV12NETWORK DIGITAL INPUT 11
BV13NETWORK DIGITAL INPUT 12
BV14NETWORK DIGITAL INPUT 13
BV15NETWORK DIGITAL INPUT 14
BV16NETWORK DIGITAL INPUT 15
BV17NETWORK DIGITAL INPUT 16

Properties​

List of available properties for the Network Digital Input objects. Properties with an identifier of 512 or higher are proprietary.

Property IdentifierProperty IDProperty DatatypeWritable / Read-only
Object_Identifier75BACnetObjectIdentifierR
Object_Name77CharacterStringR
Object_Type79BACnetObjectTypeR
Present_Value85BACnetBinaryPVW (commandable)
Status_Flags111BACnetStatusFlagsR
Event_State36BACnetEventStateR
Out_Of_Service81BOOLEANW
Priority_Array87BACnetPriorityArrayR
Relinquish_Default104BACnetBinaryPVR
Property_List371BACnetARRAY of UnsignedR
Description28CharacterStringR
Reliability103BACnetReliabilityR
Active_Text4CharacterStringR
Inactive_Text46CharacterStringR
Group_Command_Allowed532EnumeratedW

Proprietary Properties​

Group_Command_Allowed (532)​

Controls whether this network digital input is allowed to be used in the control. The Present_Value stays writable at all times. This property only gates whether the operation acts on the binary input value. The values are as follows:

  • 0 - the input cannot command the output active or inactive.
  • 1 - the input can only command the output inactive.
  • 2 - the input can only command the output active.
  • 3 - the input can command the output active or inactive.

The default value is 3.