Analog Input Object - Voltage

These Analog Input objects report the voltage-related analog measurements read by the CC-ONYX controller: the feedback of the two 0-10V outputs, the two 0-10V inputs, and the 24VDC output feedback. All values are expressed as a percentage from 0 to 100.

Objects​

TypeInstanceNameMinimumMaximumUnitPhysical signal
AI0OUTPUT 0-10V 1 FB0100percent0-10V + (1)
AI1OUTPUT 0-10V 2 FB0100percent0-10V + (2)
AI2INPUT 0-10V 10100percentAI1 - DAYLIGHT 1
AI3INPUT 0-10V 20100percentAI2 - DAYLIGHT 2
AI424VDC FB0100percent+24V OUT

Properties​

List of available properties for the Analog Input objects.

Property IdentifierProperty IDProperty DatatypeWritable / Read-only
Object_Identifier75BACnetObjectIdentifierR
Object_Name77CharacterStringR
Object_Type79BACnetObjectTypeR
Present_Value85REALR (1)
Status_Flags111BACnetStatusFlagsR
Event_State36BACnetEventStateR
Out_Of_Service81BOOLEANW
Units117BACnetEngineeringUnitsR
Property_List371BACnetARRAY of UnsignedR
Description28CharacterStringR
Reliability103BACnetReliabilityR (1)
Min_Pres_Value69REALR
Max_Pres_Value65REALR
COV_Increment22REALW
Reliability_Evaluation_Inhibit357BOOLEANW
  1. This property is writable when Out_Of_Service is TRUE.