Analog Output Object - Lamp Command
The lamp command Analog Output objects command the five lamps. These objects expose proprietary properties used to configure the DALI control gear and the lamp behaviour. All present values are expressed as a percentage from 0 to 100.
Objects
| Type | Instance | Name | Minimum | Maximum | Unit | Physical signal |
|---|---|---|---|---|---|---|
| AO | 2 | LAMP 1 CMD | 0 | 100 | percent | Lamp 1 |
| AO | 3 | LAMP 2 CMD | 0 | 100 | percent | Lamp 2 |
| AO | 4 | LAMP 3 CMD | 0 | 100 | percent | Lamp 3 |
| AO | 5 | LAMP 4 CMD | 0 | 100 | percent | Lamp 4 |
| AO | 6 | LAMP 5 CMD | 0 | 100 | percent | Lamp 5 |
Properties
The lamp command objects expose the standard analog output properties plus proprietary properties. Properties with an identifier of 512 or higher are proprietary. The dimming-level proprietary properties are expressed as a percentage from 0 to 100 after conversion from the raw DALI arc power level.
| Property Identifier | Property ID | Property Datatype | Writable / Read-only |
|---|---|---|---|
| Object_Identifier | 75 | BACnetObjectIdentifier | R |
| Object_Name | 77 | CharacterString | W |
| Object_Type | 79 | BACnetObjectType | R |
| Present_Value | 85 | REAL | W (commandable) |
| Status_Flags | 111 | BACnetStatusFlags | R |
| Event_State | 36 | BACnetEventState | R |
| Out_Of_Service | 81 | BOOLEAN | W |
| Units | 117 | BACnetEngineeringUnits | R |
| Priority_Array | 87 | BACnetPriorityArray | R |
| Relinquish_Default | 104 | REAL | R |
| Property_List | 371 | BACnetARRAY of Unsigned | R |
| Description | 28 | CharacterString | R |
| Max_Pres_Value | 65 | REAL | R |
| Active_Scene | 700 | Unsigned | R |
| Power_On_Level | 1009 | REAL | W |
| System_Failure_Level | 1010 | REAL | W |
| Minimum_Level | 1011 | REAL | W |
| Maximum_Level | 1012 | REAL | W |
| Type_5_Failure_Status | 1006 | Unsigned | R |
| Type_5_Converter_Status | 1007 | Unsigned | R |
| Scene_0 | 1023 | REAL | W |
| Scene_1 | 1024 | REAL | W |
| Scene_2 | 1025 | REAL | W |
| Scene_3 | 1026 | REAL | W |
| Scene_4 | 1027 | REAL | W |
| Scene_5 | 1028 | REAL | W |
| Scene_6 | 1029 | REAL | W |
| Scene_7 | 1030 | REAL | W |
| Scene_8 | 1031 | REAL | W |
| Scene_9 | 1032 | REAL | W |
| Scene_10 | 1033 | REAL | W |
| Scene_11 | 1034 | REAL | W |
| Scene_12 | 1035 | REAL | W |
| Scene_13 | 1036 | REAL | W |
| Scene_14 | 1037 | REAL | W |
| Scene_15 | 1038 | REAL | W |
| Operating_Mode | 1040 | Unsigned | W |
| Type_5_Dimming_Curve | 1041 | Unsigned | W |
| Up_Switch_On_Threshold | 1043 | REAL | W |
| Up_Switch_Off_Threshold | 1044 | REAL | W |
| Down_Switch_On_Threshold | 1045 | REAL | W |
| Down_Switch_Off_Threshold | 1046 | REAL | W |
| Phys_Min_Level | 1142 | REAL | R |
| Type_5_Converter_Features | 1149 | Unsigned | R |
| Fade_Mode | 2001 | Unsigned | W |
| Run_Hour | 2002 | Unsigned | W |
| Occupancy_Delay_Off | 2003 | Unsigned | W |
| Default_Fade_Time | 2374 | Unsigned | W |
Proprietary Properties
Scene
Active_Scene (700)
Reports the scene number currently applied to the lamp. This property is read-only.
DALI dimming levels
These properties map to the DALI dimming registers of the controller, which emulates a DALI control gear to drive its 0-10V and relay outputs. Each value is read and written as a percentage from 0 to 100.
Power_On_Level (1009)
Arc power level the controller applies when it powers on.
System_Failure_Level (1010)
Arc power level the controller applies when a bus failure is detected.
Minimum_Level (1011)
Lowest dimming level the controller is allowed to reach.
Maximum_Level (1012)
Highest dimming level the controller is allowed to reach.
Phys_Min_Level (1142)
Physical minimum level supported by the controller hardware. Read-only.
DALI scene levels
Scene_0 to Scene_15 (1023 to 1038)
The sixteen DALI scene levels stored in the controller. Each property holds the dimming level, as a percentage, applied when the matching DALI scene is recalled.
DALI Device Operating Mode
Operating_Mode (1040)
Selects the DALI device type emulated by the lamp. The value determines which of the type-specific sections below applies. The values are as follows:
- 0 (0x00) - DC converter (Device Type 5).
- 128 (0x80) - Switching function (Device Type 7).
- 129 (0x81) - Colour temperature Tc (Device Type 8).
DALI switching thresholds (Device Type 7)
These properties configure the switching behaviour of a Device Type 7 (switching function) control gear. Each threshold is expressed as a percentage.
Up_Switch_On_Threshold (1043)
Level at or above which the up-switch turns on.
Up_Switch_Off_Threshold (1044)
Level at or below which the up-switch turns off.
Down_Switch_On_Threshold (1045)
Level at or above which the down-switch turns on.
Down_Switch_Off_Threshold (1046)
Level at or below which the down-switch turns off.
DALI DC converter (Device Type 5)
These properties configure and report a Device Type 5 (DC voltage) converter.
Type_5_Dimming_Curve (1041)
Selects the dimming curve applied by the converter. The values are as follows:
- 0 - logarithmic.
- 1 - linear.
Type_5_Failure_Status (1006)
Converter failure status reported by the controller. Read-only.
Type_5_Converter_Status (1007)
Converter status bitmask. Read-only.
| Bit | Description |
|---|---|
| 0 | 0-10V output active |
| 1 | Pull-up active |
| 2 | Non-logarithmic dimming curve active |
Type_5_Converter_Features (1149)
Converter feature bitmask reported by the controller. Read-only.
| Bit | Description |
|---|---|
| 0 | 0-10V output selectable |
| 1 | Pull-up selectable |
| 2 | Output fault detection supported |
| 3 | Mains relay present |
| 4 | Output level query supported |
| 5 | Non-logarithmic dimming curve supported |
Configuration
These properties configure how the lamp reacts to commands and occupancy.
Fade_Mode (2001)
Dim mode applied to BACnet writes on this lamp. The values are as follows:
- 0 - no fade, the level changes immediately.
- 1 - fade, the level changes using the configured fade time.
Run_Hour (2002)
Accumulated running hours, in hours, of the lamp.
Occupancy_Delay_Off (2003)
Delay, in seconds, before the lamp turns off after the space becomes unoccupied.
Default_Fade_Time (2374)
Default DALI fade time, in milliseconds, applied to level changes. A value of 0 falls back to the standard DALI fade time.