Binary Value Object - Occupancy State
The Occupancy State binary value objects report the computed occupancy state of each control output. These objects are read-only.
Objects
| Type | Instance | Name |
|---|---|---|
| BV | 100 | CONTROL OUTPUT 1 - OCCUPANCY STATE |
| BV | 200 | CONTROL OUTPUT 2 - OCCUPANCY STATE |
| BV | 300 | CONTROL OUTPUT 3 - OCCUPANCY STATE |
| BV | 400 | CONTROL OUTPUT 4 - OCCUPANCY STATE |
| BV | 500 | CONTROL OUTPUT 5 - OCCUPANCY STATE |
Properties
List of available properties for the Occupancy State objects.
| Property Identifier | Property ID | Property Datatype | Writable / Read-only |
|---|---|---|---|
| Object_Identifier | 75 | BACnetObjectIdentifier | R |
| Object_Name | 77 | CharacterString | R |
| Object_Type | 79 | BACnetObjectType | R |
| Present_Value | 85 | BACnetBinaryPV | R |
| Status_Flags | 111 | BACnetStatusFlags | R |
| Event_State | 36 | BACnetEventState | R |
| Out_Of_Service | 81 | BOOLEAN | W |
| Relinquish_Default | 104 | BACnetBinaryPV | R |
| Property_List | 371 | BACnetARRAY of Unsigned | R |
| Description | 28 | CharacterString | R |
| Reliability | 103 | BACnetReliability | R |
| Active_Text | 4 | CharacterString | R |
| Inactive_Text | 46 | CharacterString | R |