Skip to main content

Analog Output Object - 0-10V

The 0-10V Analog Output objects command the two general-purpose 0-10V analog outputs. All present values are expressed as a percentage from 0 to 100.

Objects​

TypeInstanceNameMinimumMaximumUnitPhysical signal
AO0OUTPUT 0-10V 10100percentOUTPUT 0-10V 1
AO1OUTPUT 0-10V 20100percentOUTPUT 0-10V 2

Properties​

Property IdentifierProperty IDProperty DatatypeWritable / Read-only
Object_Identifier75BACnetObjectIdentifierR
Object_Name77CharacterStringR
Object_Type79BACnetObjectTypeR
Present_Value85REALW (commandable)
Status_Flags111BACnetStatusFlagsR
Event_State36BACnetEventStateR
Out_Of_Service81BOOLEANW
Units117BACnetEngineeringUnitsR
Priority_Array87BACnetPriorityArrayR
Relinquish_Default104REALR
Property_List371BACnetARRAY of UnsignedR
Description28CharacterStringR