Analog Output Object - 0-10V
The 0-10V Analog Output objects command the two general-purpose 0-10V analog outputs. All present values are expressed as a percentage from 0 to 100.
Objects
| Type | Instance | Name | Minimum | Maximum | Unit | Physical signal |
|---|
| AO | 0 | OUTPUT 0-10V 1 | 0 | 100 | percent | OUTPUT 0-10V 1 |
| AO | 1 | OUTPUT 0-10V 2 | 0 | 100 | percent | OUTPUT 0-10V 2 |
Properties
| Property Identifier | Property ID | Property Datatype | Writable / Read-only |
|---|
| Object_Identifier | 75 | BACnetObjectIdentifier | R |
| Object_Name | 77 | CharacterString | R |
| Object_Type | 79 | BACnetObjectType | R |
| Present_Value | 85 | REAL | W (commandable) |
| Status_Flags | 111 | BACnetStatusFlags | R |
| Event_State | 36 | BACnetEventState | R |
| Out_Of_Service | 81 | BOOLEAN | W |
| Units | 117 | BACnetEngineeringUnits | R |
| Priority_Array | 87 | BACnetPriorityArray | R |
| Relinquish_Default | 104 | REAL | R |
| Property_List | 371 | BACnetARRAY of Unsigned | R |
| Description | 28 | CharacterString | R |