Binary Input Object - Local Buttons
The Binary Input button objects report the state of the six local buttons. BUTTON LOCAL STATUS is the first local button and BUTTON LOCAL 1 to 5 are the remaining ones. Each object reports whether its button is pressed.
Objects
| Type | Instance | Name |
|---|---|---|
| BI | 13 | BUTTON LOCAL STATUS |
| BI | 14 | BUTTON LOCAL 1 |
| BI | 15 | BUTTON LOCAL 2 |
| BI | 16 | BUTTON LOCAL 3 |
| BI | 17 | BUTTON LOCAL 4 |
| BI | 18 | BUTTON LOCAL 5 |
Properties
List of available properties for the Binary Input objects.
| Property Identifier | Property ID | Property Datatype | Writable / Read-only |
|---|---|---|---|
| Object_Identifier | 75 | BACnetObjectIdentifier | R |
| Object_Name | 77 | CharacterString | R |
| Object_Type | 79 | BACnetObjectType | R |
| Present_Value | 85 | BACnetBinaryPV | R (1) |
| Status_Flags | 111 | BACnetStatusFlags | R |
| Event_State | 36 | BACnetEventState | R |
| Out_Of_Service | 81 | BOOLEAN | W |
| Polarity | 84 | BACnetPolarity | R |
| Property_List | 371 | BACnetARRAY of Unsigned | R |
| Description | 28 | CharacterString | R |
| Reliability | 103 | BACnetReliability | R |
| Active_Text | 4 | CharacterString | R |
| Inactive_Text | 46 | CharacterString | R |
- This property is writable when Out_Of_Service is TRUE.