Modify Device

BACnet Browser Modify Device window

The Modify Device dialog lets you change the BACnet identity and MS/TP settings of the selected controller. Each field has its own Write button that sends only that value to the controller.

Device​

FieldDescription
NameBACnet device name.
IdBACnet Device instance number. It must be unique on the network.

MS/TP​

FieldDescription
MACMS/TP MAC address of the controller (0 to 127). It must be unique on the segment.
BaudrateMS/TP communication speed. It must match the rest of the segment.
Max masterHighest MAC address polled for the token on the segment.