Skip to main content

Outputs

Pulse Output​

Positive or negative rectified 24 Vac for three WR-6161 Panasonic relays.

0-10V Output​

The controller changes its output using linear voltage mode.

The 0-10Vdc output is protected against short-circuits and inverted polarity using a 140 mA fuse. The fuse automatically resets when the power supply is turned off from the dimming controller for a few seconds.

This output can drive up to 50 Philips Advance Mark 7 ballasts. The number of ballasts or LED drivers may change from manufacturers and models.

With an internal controller setting, this output can source voltage as required for some LED drivers.

RL Out / RL Com​

These are the output terminals for traditional relay control using 24 Vac or 24 Vdc. It can be set to control the power relay using normally open or normally closed logic.