Jumpers
Term.
Installing a jumper on Term activates the termination resistor of the RS-485 network.
Jp3, Jp4
Configures the dimming controller in relay mode. This avoids receiving lamp failures because the 0-10V output has no feedback.
Turn off the power supply before placing a jumper on Jp3 and Jp4.
Do not place a jumper on Jp2.
Remove jumpers Jp3 and Jp4 once the dimming controller has started.
Jp2, Jp4
Configures the dimming controller with 0-10V output and relay.
Turn off the power supply before placing a jumper on Jp2 and Jp4.
Do not place a jumper on Jp3.
Remove jumpers Jp2 and Jp4 once the dimming controller has started.
Jp4
Reset the dimming controller configuration.
Turn off the power supply before placing a jumper on Jp4.
Do not install jumpers on Jp2 or Jp3.
When placing a jumper on Jp4 two seconds after power up, the configurations are cleared. This resets the BACnet setting to default known values:
| Item | Value |
|---|---|
| Device Name | CCLDIM |
| Device Id | 14 |
| MSTP MAC | 127 |
| MSTP Baud Rate | 38400 |
Also, all DALI variables (short address, etc.) will be configured to factory values. See the Objects section in the Communication chapter.