Skip to main content

Jumpers

Term.​

Installing a jumper on Term activates the termination resistor of the RS-485 network.

Jp3, Jp4​

Configures the dimming controller in relay mode. This avoids receiving lamp failures because the 0-10V output has no feedback.

Turn off the power supply before placing a jumper on Jp3 and Jp4.

Do not place a jumper on Jp2.

Remove jumpers Jp3 and Jp4 once the dimming controller has started.

Jp2, Jp4​

Configures the dimming controller with 0-10V output and relay.

Turn off the power supply before placing a jumper on Jp2 and Jp4.

Do not place a jumper on Jp3.

Remove jumpers Jp2 and Jp4 once the dimming controller has started.

Jp4​

Reset the dimming controller configuration.

Turn off the power supply before placing a jumper on Jp4.

Do not install jumpers on Jp2 or Jp3.

When placing a jumper on Jp4 two seconds after power up, the configurations are cleared. This resets the BACnet setting to default known values:

ItemValue
Device NameCCLDIM
Device Id14
MSTP MAC127
MSTP Baud Rate38400

Also, all DALI variables (short address, etc.) will be configured to factory values. See the Objects section in the Communication chapter.