CCTHV Inputs
Digital
The two digital inputs must be used with COM2. Terminal COM2 supplies 30Vdc and the digital inputs sense if this voltage is present or not. A contact must be closed between COM2 and one of the inputs to detect a signal. Those inputs are optically isolated.
0-10Vdc
This input could read as a 0 to 100% and °C value using the corresponding BACnet objects.
The thermostat algorithm can use a remote temperature sensor instead of the internal sensor. See the "Temperature" section.
The input impedance is 30KΩ.
Remote temperature
Terminals used for a remote temperature sensor of 10KΩ @ 25°C. Here are some compatible temperature curves:
-
Dale curve #1
-
ATP curve Z
-
BAPI curve #2
-
Mamac curve #12
-
Greystone curve #2.
The thermostat algorithm can use the remote temperature sensor instead of the internal sensor. See the "Temperature" section.